In accordance with BS5839, a landlord's property must have a fire alarm certificate. It is recommended that all types of detectors be examined by a fire alarm certified professional at least once a year. In addition, the fire alarm test should be recorded in the log book.
DAILY CHECKLIST OF FIRE ALARM
- The alarm panel is set up properly
- Any defect notifications must be addressed
- A visual check of the panel is performed
- Make a weekly sound alarm to ensure your sound gadget is operating correctly.
- If any problems are discovered, they must be reported to the appropriate maintenance team, and a record of the mistake must be kept.
During a fire alarm inspection, there are 2-grade rules that should be observed
1. Grade A Fire Alarm System: The parameters listed below should be examined for the grade A fire alarm system.
- CO2 Alarm Detector
- Bell or Alarm Sound Device
- Central Control Board
- Manual Call Board
- Smoke Alarm Detector
- Heat Alarm Detector
2. Grade D Fire Alarm System
- The majority of the time, a Grade D fire alarm system is coupled to smoke or heat alarms, and this arrangement is most often encountered in residential homes.
- For the comprehensive exam on the fire alarm certificate, you will need to work out for 6 months.
- Every six months, the fire alarm system should be thoroughly tested. A competent person must authorise the exam. The fire alarm evaluation should be kept up to date in line with section 6 of BS5839 part 1. You will receive a fire alarm certificate after you have completed your fire alarm testing in the proper manner.
Fire alarm certificate cost
On the fire alarm equipment, Do you need secure cable testing?
Your fire alarm system’s cabling should also be examined. It may be done every five years in conjunction with an EICR electrical certificate. The electrical installation condition report must be completed in accordance with British Standard BS7671.